Portable assembled unit, 650 lb max wt, liftable by fork lift, consists of 5 480v circuits of 2 3-pole 225 amp circuit breakers w/lugs only, 1 3-pole 30 amp circuit breaker feeding the input side of a 15kva 480 delta, 208/120v, 3 phase, dry transformer, 1 2-pole 100 amp and 2 2-pole 50 amp circuit breakers w/lugs only to be connected on the 208/120v side of the transformer, 2 3-pole 30 amp circuit breakers protecting two receptacles, nema configuration l21-30r and 14 1-pole 20 amp circuit breakers of the ground fault type, ul approved, protecting fourteen receptacles, nema configurations l5-20r, ground lug to accommodate a no. 1 or 2 awg copper wire, all circuit breakers to conform to federal specification w-c-375
No other part numbers with same form, fit, and function found.
NSN 7035-01-145-5059